BAPI 54001 Wireless Receiver and Digital Output Modules

konecview in Identifikacija
The Wireless Receiver collects the data from up to 28 wireless sensors. The data is then integrated into the BMS by a BACnet MS/TP or Modbus RTU module, a BACnet IP module, or analog output modules.
The BACnet MS/TP or Modbus RTU module converts the data for integration into the RS-485 field communication network and supports up to 28 wireless sensors.
The BACnet IP module converts the data for integration into the BMS ethernet communication network and supports up to 28 wireless sensors.
Setup Step 1 – Pairing the Sensors to the Receiver
The installation process requires that each wireless sensor is paired to its associated receiver. The pairing process is easiest on a test bench with the sensors and receiver near each other.
- Select the sensor that you wish to pair to the receiver and apply power to the sensor. See its manual for detailed instructions.
- Napajajte sprejemnik. Modra lučka LED na sprejemniku bo zasvetila in ostala prižgana.
- Pritisnite in držite "servisni gumb" na vrhu sprejemnika, dokler modra LED lučka ne začne utripati, nato pritisnite in spustite "servisni gumb" na senzorju (sliki 2 in 3), ki ga želite seznaniti s sprejemnikom. Ko lučka LED na sprejemniku ponovno sveti »Vklopljeno« in zelena lučka »Service LED« na vezju senzorja trikrat hitro utripne, je seznanjanje končano. Ta postopek ponovite za vse senzorje.
Note: Pairing is not needed for the output modules, only the sensors and receiver. When the BACnet MS/TP or Modbus RTU module, or the BACnet IP module are connected to the receiver, the modules will “Auto-Discover” all the sensors that are paired with the receiver.

Setup Step 2 – Mounting and Locating of Antenna
Antena ima magnetno podlago za pritrditev. Čeprav je sprejemnik lahko v kovinskem ohišju, mora biti antena zunaj ohišja. Od vseh senzorjev do antene mora obstajati nekovinska linija vidnega polja. Sprejemljiva vidna linija vključuje stene iz lesa, pločevine ali mavca z nekovinsko letvijo. Usmerjenost antene (vodoravna ali navpična) prav tako vpliva na delovanje in se razlikuje glede na aplikacijo.
Namestitev antene na kovinsko površino bo prekinila sprejem izza površine. Zamrznjena okna lahko tudi blokirajo sprejem. Lesena ali plastična obloga, pritrjena na stropni nosilec, je odličen nosilec. Anteno lahko obesite na katero koli stropno napeljavo z vlakneno ali plastično vrvico. Za obešanje ne uporabljajte žice in ne uporabljajte perforiranih kovinskih trakov, običajno imenovanih vodovodni trak.
Setup Step 3 – Mounting of Receiver and Output Modules
Sprejemnik in izhodni moduli so lahko snaptrack, DIN letev ali površinsko nameščeni. Vsak sprejemnik lahko sprejme do 127 modulov. Začnite s sprejemnikom na skrajni levi strani, nato varno pritrdite vsak izhodni modul na desno.
Push in the blue mounting tabs to mount in 2.75” snaptrack (Fig 4). Push out the mounting tabs for DIN Rail (Fig 5). Catch the EZ mount hook on the edge of the DIN rail (Fig 6) and rotate into place. Push out the mounting tabs for surface mounting using the four supplied screws, one in each tab (Fig 7).
Če se vaši izhodni moduli zaradi omejenega prostora ne morejo prilegati v eno ravno linijo, namestite drugi niz modulov zgoraj ali spodaj. Povežite žice z desne strani prvega niza modulov na levo stran drugega niza modulov.
This configuration requires one or more Pluggable Terminal Block Connector Kits (BA/AOM-CONN) for the extra wire terminations on the left and right side of the output modules. Each kit includes one set of 4 connectors.

Setup Step 4 – Termination
The receiver and output modules are pluggable and can be connected in an attached string as shown at right. The power for the output modules is supplied by the receiver in this configuration. If the modules are powered separately rather than from the receiver (as shown below), then they must have 15 to 24VDC. Be sure that you supply enough power for all the devices on the bus.
Note: The receiver can accommodate up to 127 different output modules; however, only 10 modules can be powered directly from the receiver. To add additional modules, follow the “Extending the Serial Network” directions on pg 4. 
Setup Step 5 – Receiver Switch Settings
Vse nastavitve senzorjev nadzoruje in prilagaja sprejemnik, da ustrezajo potrebam namestitve. Te prilagodite z DIP stikali na vrhu sprejemnika. To so nastavitve za VSE SENZORJE, ki so seznanjeni s tem sprejemnikom.
- Sample Hitrost/Interval – čas med tem, ko se senzor zbudi in odčita. Razpoložljive vrednosti 30 s, 1 min, 3 min ali 5 min.
- Hitrost prenosa/interval – čas med tem, ko senzor prenese odčitke sprejemniku. Razpoložljive vrednosti so 1, 5, 10 ali 30 minut.
- Temperature Delta – The change in temperature between a sample and the last transmission that will cause the sensor to override the transmit interval and immediately transmit all values to the receiver. The available values are 1 or 3 °F or °C.
- Humidity Delta – The change in humidity between a sample and the last transmission that will cause the sensor to override the transmit interval and immediately transmit all values to the receiver. The available values are 3 or 5 %RH.

Extending the Serial Network Between the Receiver and Modules or Powering Additional Groups of Modules
The output modules may be mounted up to 4,000 feet (1,200 meters) away from the receiver using the configuration shown in Fig 11. The total length of all the shielded, twisted pair cables shown in Fig. 11 is 4,000 feet (1,200 meters). If the distance from the receiver to the group of output modules is greater than 100 feet (30 meters), provide a separate power supply or voltage converter (such as BAPI’s VC350A EZ) for that group of output modules.
Also, each receiver can accommodate up to 127 different output modules; however, only 10 modules can be powered directly from the receiver. Follow the directions shown here to add additional modules.

Resetting a Sensor, Receiver or Output Module
Senzorji, sprejemniki in izhodni moduli ostanejo seznanjeni med seboj, ko je napajanje prekinjeno ali so baterije odstranjene. Če želite prekiniti vezi med njimi, je treba enote ponastaviti, kot je opisano spodaj:
- ZA PONASTAVITEV SENZORJA:
Press and hold the “Service Button” on the sensor for about 30 seconds. During those 30 seconds, the green LED will be off for about 5 seconds, then flash slowly, then begin flashing rapidly. When the rapid flashing stops, the reset is complete. The sensor can now be paired to a new receiver. Sensors that were previously discovered by the Digital Output Modules will not need to be rediscovered. - TO RESET A DIGITAL OUTPUT MODULE:
Press and hold the “Service Button” on the top of the unit for 10 seconds – the LED will go solid for 2 seconds and all the BACnet, Ethernet, and Serial Settings will be erased. Holding down the service button for an additional 20 seconds, the LED will go solid for 4 seconds and all the sensor objects will be erased. - ZA PONASTAVITEV SPREJEMNIKA:
Press and hold the “Service Button” on the sensor for about 20 seconds. During those 20 seconds, the blue LED will flash slowly, then begin flashing rapidly. When the rapid flashing stops and returns to solid blue, the reset is complete. The unit can now be re-paired to the output modules. Caution! Resetting the receiver will break the bonds between the receiver and all sensors. The sensors will need to be re-paired with the receiver. - Privzeto stanje, ko je brezžični prenos prekinjen
If an output module does not receive data from a paired sensor for 35 minutes, an error state will happen to indicate this. If this happens, the individual output modules will react as described below. Once a transmission is received, the output modules will revert to normal operation in 5 seconds or less.
BACnet IP Module: Each sensor object has an “Event State” property which will turn from a Normal state to a Fault state, and there is a “Reliability” property which will indicate a “Communication Failure”
BACnet MS/TP or Modbus RTU Module: When the module is in Modbus mode, there is an error register for each sensor object and the value of the register will become 1 when timed out. When the module is in BACnet mode, each sensor object has an “Event State” property which will turn from a Normal state to a Fault state, and there is a “Reliability” property which will indicate a “Communication Failure”.
Diagnostika brezžičnega sistema
Možne težave:
Odčitek s senzorja je nepravilen ali na spodnji meji:
Možne rešitve:
- Press the sensor’s “Service” button (as described in the “Pairing the Sensors to the Receiver” section on pg 1) and verify that the green LED on the sensor circuit board flashes. If not, replace the batteries.
- Press the sensor’s “Service” button and verify that the LEDs on the receiver and the output module blink. If they do not, try resetting then re-pairing the sensor to the receiver.
- Check for proper wiring and connections from the receiver to the output modules.
The LED on the output module is blinking rapidly:
This only occurs on a hardware error. Try power cycling the device or contact BAPI for additional assistance.
Specifikacije
Sprejemnik
- Supply Power: 15 to 24 VDC (from half-wave rectified supply)
- Poraba energije: 30 mA pri 24 VDC
- Safety Current: 200 mA
- Kapaciteta/enota:
- Up to 28 sensors | Up to 127 different output modules
- Reception Distance: Varies by application*
- Frekvenca: 2.4 GHz (Bluetooth Low Energy)
- Bus Cable Distance: 4,000 feet (1,200 meters)
- Okoljsko območje delovanja:
- Temp: 32 to 140°F (0 to 60°C) | Humidity: 5 to 95% RH non-condensing
- Enclosure Material & Rating: ABS Plastic, UL94 V-0 (Indoor use only)
- Agency: RoHS / Contains FCC ID: QOQGM210P / IC: 5123A-GM210P
- *Razpon v stavbi je odvisen od ovir, kot so pohištvo in stene, ter gostote teh materialov. V širokih odprtih prostorih je lahko razdalja večja; v gostih prostorih je lahko razdalja manjša.

BACnet IP Module
- Supply Power: 15 to 24 VDC (from half-wave rectified supply), or powered through the receiver if connected.
- Note on Power: If powering the module separately, only use a power supply with a fuse or current limiting feature. The exact type of supply (fused DC, current-limited, or a wireless receiver with protection) is up to the installer.
- Power Consumption: 40 mA max @ 24 VDC
- Lost Communication Timeout: 35 minutes
- Ethernet Standard: 10/100BASE-TX
- Okoljsko območje delovanja:
- Temperatura: 32 do 140 °F (0 do 60 °C)
- Vlažnost: 5 do 95 % RH brez kondenzacije
- Encl. Material & Rating: ABS Plastic, UL94 V-0 (Indoor use only)
- Agency: RoHS (CE pending)
BACnet MS/TP or Modbus RTU Module
- Supply Power: 15 to 24 VDC (from half-wave rectified supply), or powered through the receiver if connected.
- Note on Power: If powering the module separately, only use a power supply with a
- fuse or current limiting feature. The exact type of supply (fused DC, current-limited,
- or a wireless receiver with protection) is up to the installer.
- Power Consumption: 40 mA max @ 24 VDC
- Lost Communication Timeout: 35 minutes
- Bus Cable Distance: 4,000 feet (1,200 meters)
- Okoljsko območje delovanja:
- Temp: 32 to 140°F (0 to 60°C) | Humidity: 5 to 95% RH non-condensing
- Encl. Material & Rating: ABS Plastic, UL94 V-0 (Indoor use only)
- Agency: RoHS (CE pending)

Certifikati agencije
RoHS / Contains FCC ID: QOQGM210P / IC: 5123A-GM210 / Independent Communications Authority of South Africa
Ta naprava je skladna s 15. delom pravil FCC. Delovanje je odvisno od naslednjih dveh pogojev:
- Ta naprava morda ne povzroča škodljivih motenj in
- Ta naprava mora sprejeti vse prejete motnje, vključno z motnjami, ki lahko povzročijo neželeno delovanje.
- Vse spremembe ali modifikacije, ki jih BAPI izrecno ne odobri, lahko razveljavijo uporabnikovo pooblastilo za uporabo opreme.
- Ta naprava je skladna s standardom(i) RSS Industry Canada (IC). Delovanje je odvisno od naslednjih dveh pogojev.
- Ta naprava morda ne povzroča motenj.
- Ta naprava mora sprejeti vse motnje, vključno z motnjami, ki lahko povzročijo neželeno delovanje naprave.
BACnet MS/TP or Modbus RTU Module Configuration Utility
Before configuring the module, all of the sensors in your system need to be paired with the receiver as described earlier in this instructions document. The module also needs to be connected with the receiver long enough that it has received at least one transmission from each of the sensors.
Module in BACnet MS/TP Mode
To configure the device, follow the steps below.
- Open a browser on your computer and go to the BACnet MS/TP or Modbus RTU Module product page on the BAPI webmesto. Prenesite .zip file in izvlecite vsebino.
- Double click the “BAPI.DeviceConfiguration. exe” file to run the utility.
- Connect a USB cable between your computer and the USB-C connector on the module. The data for the device settings will populate the Device Utility Information Window (Fig 1). Note: The module does not need to be powered for the configuration. The USB-C cable will provide the
- Edit the values in the Serial Settings section of the Device Configuration Window for your application. Select BACnet as the Output Protocol and the Protocol Settings section below the Serial Settings will be shown.
- Click Advanced Options to open the Advanced Options window (Fig 2). Click the Select Object Dropdown to choose one of the available objects for that sensor (Fig 3). Edit the Object Name and Change of Value Delta fields if desired. Click Submit to save your changes to the sensor before selecting the next sensor. Select Delete option to remove any objects.
- Kliknite Pošlji, da shranite spremembe senzorja, preden izberete naslednji objekt.
- When completed with the last object, click Submit and then Close to return to the main window.
- If any settings are changed, please restart the device by clicking on the Restart Device button at the bottom of the configuration tool, which will perform a power cycle operation and apply the new settings.
- The configuration is now complete so you can disconnect the USB cable.
BACnet MS/TP or Modbus RTU Module Configuration Utility continued…
Before configuring the module, all of the sensors in your system need to be paired with the receiver as described as described earlier in this instructions document. The module also needs to be connected with the receiver long enough that it has received at least one transmission from each of the sensors.
Module in Modbus RTU Mode
To configure the utility, follow the steps below.

- Open a browser on your computer and go to the BACnet MS/TP or Modbus RTU Module product page on the BAPI webmesto. Prenesite .zip file in izvlecite vsebino.
- Double click the “BAPI.DeviceConfiguration. exe” file to run the utility.
- Connect a USB cable between your computer and the USB-C connector on the module. The data for the device settings will populate the Device Configuration Window (Fig 4). Note: The module does not need to be powered for the configuration. The USB-C cable will provide the necessary power.
Edit the values in the Serial Settings section of the Device Utility Information Window for your application. Select Modbus as the Output Protocol and the Download Modbus Map button appears. - When using Modbus RTU as the output protocol, it is essential to download the Modbus map. After downloading, open the accompanying Modbus map spreadsheet (Fig 5). You can rename the file as desired or keep the original name. Once you have saved the file, all the necessary information will be readily available for updating the settings in your controller and BMS.
- If any settings are changed, please restart the device by clicking on the Restart Device button at the bottom of the configuration tool, which will perform a power cycle operation and apply the new settings.
- Zdaj lahko odklopite kabel USB.

BACnet IP Module Configuration Utility:
To configure the module, follow the steps below.
- Power the module using the BLE Receiver.
- Connect the module using the Ethernet port to a network with a DHCP server. The DHCP server will assign a Private IP address to the module.
- Use a BACnet discovery tool or the one included in a BMS controller to find the device’s IP address. The factory default for the BACnet interface is running on UDP port 47808. Open a web browser and enter the IP address to access the device’s web interface. You will need to log in with the following default credentials:
- Upon login, please make all the necessary changes to network settings (Fig 6), device settings (Fig 7), object settings (Fig 8) and user details.
- If you want to reset the module please press and hold the “Service Button” on the top of the unit for 10 seconds, the LED will go solid for 2 seconds and all device settings willbe erased. Holding down the “Service Button” for additional 20 seconds, the LED will go solid for 4 seconds and all the sensor objects will be erased.