Danfoss KVR15 Pressure Regulator Instruction Manual

Model: 034L0097

1. Uvod

This manual provides essential information for the safe and efficient installation, operation, and maintenance of the Danfoss KVR15 Pressure Regulator. The KVR15 is designed to maintain a constant evaporating pressure in refrigeration and air conditioning systems. It features a 5/8 inch ODF connection and an access port for pressure measurement.

Please read this manual thoroughly before installing or operating the unit. Keep this manual for future reference.

2. Varnostne informacije

WARNING: Improper installation, operation, or maintenance can result in serious injury or equipment damage.

3. Vsebina paketa

Po razpakiranju preverite, ali so vse komponente prisotne in nepoškodovane:

Danfoss KVR15 Pressure Regulator with 5/8 inch ODF connections and an access port

Image: Danfoss KVR15 Pressure Regulator. This image shows the compact design of the regulator, highlighting its 5/8 inch ODF connections on both ends and a small access port located on the side for pressure monitoring.

4. Nastavitev in namestitev

Follow these steps for proper installation of the KVR15 Pressure Regulator:

  1. Priprava sistema: Ensure the refrigeration system is depressurized and isolated before beginning installation.
  2. Lokacija: Install the regulator in the suction line, upstream of the compressor, and preferably in a horizontal pipe run. Ensure there is sufficient space for service and adjustment.
  3. Povezava: The KVR15 features 5/8 inch ODF (Outside Diameter Flare) connections. Use appropriate brazing techniques for copper tubing. Ensure the regulator is clean and free of debris before brazing. Protect the valve body from excessive heat during brazing by wrapping it with a wet cloth or using a heat sink compound.
  4. Smer toka: Observe the arrow on the regulator body, which indicates the correct flow direction. Install the regulator so that the refrigerant flows in the direction of the arrow.
  5. Vrata za dostop: The access port allows for pressure measurement. Ensure the cap is securely tightened after use to prevent leaks.
  6. Test puščanja: After installation, perform a thorough leak test on all connections using an appropriate leak detection method.
  7. Evakuacija: Evacuate the system to the required vacuum level before charging with refrigerant.

Priporočena orodja: Brazing torch, nitrogen for purging, leak detector, vacuum pump, manifold gauge set, pipe cutters, deburring tool, wet rags or heat sink compound.

5. Navodila za uporabo

The KVR15 regulator is designed to maintain a constant evaporating pressure. Adjustment is typically performed during system commissioning.

  1. Začetna nastavitev: The regulator is factory set to a nominal pressure. For specific system requirements, adjustment may be necessary.
  2. Prilagoditev tlaka:
    • Remove the protective cap from the adjustment spindle.
    • Turn the adjustment spindle clockwise to increase the evaporating pressure.
    • Turn the adjustment spindle counter-clockwise to decrease the evaporating pressure.
    • Use a pressure gauge connected to the access port or elsewhere in the suction line to monitor the pressure while adjusting.
    • Make small adjustments and allow the system to stabilize before making further changes.
    • Once the desired pressure is achieved, replace and tighten the protective cap to secure the setting and prevent leaks.
  3. Access Port Usage: The access port allows for temporary connection of a pressure gauge to verify the regulated pressure. Always ensure the port cap is securely tightened when not in use.

6. Vzdrževanje

The Danfoss KVR15 Pressure Regulator is designed for long-term, reliable operation with minimal maintenance. However, periodic checks are recommended.

Opomba: Internal components of the KVR15 are not user-serviceable. If the regulator malfunctions, it should be replaced by a qualified technician.

7. Odpravljanje težav

This section provides solutions to common issues that may arise with the KVR15 Pressure Regulator.

TežavaMožen vzrokrešitev
Regulated pressure is too high/low.Incorrect adjustment setting.Adjust the regulator setting as described in the "Operating Instructions" section.
Pressure fluctuates significantly.System instability; debris in regulator; incorrect sizing.Check for system issues (e.g., TXV operation). If debris is suspected, the regulator may need replacement. Verify regulator sizing for the application.
Refrigerant leak at connections.Improper brazing; loose access port cap.Re-braze connections if necessary. Ensure access port cap is securely tightened.
No pressure regulation.Internal failure; completely clogged.The regulator may need to be replaced. Consult a qualified technician.

If troubleshooting steps do not resolve the issue, contact a qualified HVAC/R technician or Danfoss technical support.

8. Specifikacije

FunkcijaPodrobnost
ZnamkaDanfoss
Številka modela034L0097
VrstaEvaporating Pressure Regulator (KVR15)
Velikost povezave5/8 inch ODF (Outside Diameter Flare)
Merilni sistemPalec
LastnostiDostopna vrata
ProizvajalecDanfoss
ASINB0085POK2G
Prvič na voljo27. december 2017

9. Informacije o garanciji

Danfoss products are manufactured to high-quality standards. This product is covered by Danfoss's standard manufacturer's warranty. Specific warranty terms and conditions, including duration and coverage details, can be found on the official Danfoss website or by contacting Danfoss customer service. Please retain your proof of purchase for warranty claims.

Opomba: The warranty may be voided by improper installation, unauthorized modifications, or use outside of specified operating conditions.

10. Podpora strankam

For technical assistance, spare parts, or further information regarding the Danfoss KVR15 Pressure Regulator, please visit the official Danfoss webspletno mesto ali se obrnite na njihov oddelek za podporo strankam.

Danfossov uradnik Webspletno mesto: www.danfoss.com

When contacting support, please have your product model number (034L0097) and serial number (if applicable) ready.

Povezani dokumenti - 034L0097

Prejview Navodila za namestitev digitalnega regulatorja Danfoss ERC 214
Celovit priročnik za namestitev digitalnega regulatorja Danfoss ERC 214, ki podrobno opisuje njegove funkcije, uporabniški vmesnik, konfiguracijo za hiter zagon, osnovne funkcije, tehnične podatke in nastavitve parametrov za hlajenje in odmrzovanje.
Prejview Navodila za namestitev tlačnega stikala Danfoss serije RT
Ta priročnik vsebuje navodila za namestitev tlačnih stikal Danfoss serije RT, vključno z modeli RT 6W, RT 6B, RT 6S, RT 6AW, RT 6AB, RT 6AS, RT 30AW, RT 30AB in RT 30AS. Zajema značilnosti izdelka, tehnične specifikacije, postopke montaže, električne povezave in nastavitve, z odobritvami po standardu EN 12263 in oznako CE.
Prejview Navodila za namestitev tlačnega stikala Danfoss KPI 34, 35, 36, 38
Navodila za montažo tlačnih stikal Danfoss serije KPI (KPI 34, 35, 36, 38) s podrobnimi specifikacijami, temperaturnimi omejitvami, tlačnimi območji, diferencialnimi nastavitvami, električnimi nazivnimi vrednostmi in navodili za ožičenje.
Prejview Navodila za namestitev diferencialnega tlačnega stikala Danfoss MP 54, MP 55, MP 55A
Navodila za montažo diferencialnih tlačnih stikal Danfoss MP 54, MP 55 in MP 55A, ki podrobno opisujejo združljivost hladilnih sredstev, tehnične specifikacije in postopke montaže.
Prejview Danfoss ERC 213 Navodila za namestitev elektronskega nadzora hlajenja
Navodila za namestitev elektronskega krmilnika hlajenja Danfoss ERC 213, ki podrobno opisujejo njegove tehnične značilnosti, uporabniški vmesnik, dimenzije, električne povezave in nastavitve parametrov za komercialne hladilne aplikacije.
Prejview Danfoss AVDA Instruction Manual
Comprehensive instruction manual for the Danfoss AVDA valve, detailing installation, function adjustment, troubleshooting, and spare parts for industrial applications.