1. Uvod in predstavitev izdelkaview
This manual provides essential information for the safe and effective use of the GE SELA36AT0150 Bolt-On Mount Type SEL Molded Case Circuit Breaker. This current-limiting circuit breaker is designed for industrial and commercial applications, providing protection against overcurrents and short circuits.
Glavne lastnosti vključujejo:
- Current Limiting Circuit Breaker: Designed to limit the magnitude and duration of short-circuit currents.
- 150 Amps Max | 150 A Rating Plug: Configured for a maximum current of 150 Amps with a corresponding rating plug.
- 3 Pole, 480/600 VAC: Suitable for three-phase alternating current systems up to 600 Volts.
- Spectra RMS Series: Part of the GE Spectra RMS line, known for advanced protection features.
- Bolt-On Mount: Designed for secure bolt-on installation.

Slika 1: Spredaj view of the GE SELA36AT0150 Circuit Breaker, showing the ON/OFF switch and product labels.
2. Varnostne informacije
OPOZORILO: Installation, maintenance, and troubleshooting of electrical equipment should only be performed by qualified and licensed electricians. Failure to follow these instructions can result in serious injury, death, or property damage.
- Always disconnect power before working on electrical circuits or equipment.
- Uporabljajte ustrezno osebno zaščitno opremo (OZO), vključno z izoliranimi rokavicami in zaščito za oči.
- Verify all connections are secure and properly torqued according to specifications.
- Ensure the circuit breaker's ratings match the system requirements.
3. Nastavitev in namestitev
The GE SELA36AT0150 is a bolt-on mount circuit breaker. Proper installation is crucial for safe and reliable operation.
3.1 Preverjanja pred namestitvijo
- Confirm the circuit breaker's voltage, current, and interrupting ratings are compatible with the electrical system.
- Inspect the circuit breaker for any physical damage. Do not install damaged units.
- Prepričajte se, da je površina za montažo čista, suha in strukturno trdna.
3.2 Navodila za montažo
- De-energize the electrical panel or system where the breaker will be installed. Verify zero voltage z multimetrom.
- Position the circuit breaker in the designated slot or mounting location.
- Secure the breaker using appropriate bolts and hardware for bolt-on mounting. Ensure it is firmly seated.
- Connect the load and line conductors to the appropriate terminals. The breaker includes a set of bottom lugs.
- Refer to the product label for specific wire ranges and torque specifications:
- Wire Range: #12 - 3/0 CU, #12 - 3/0 AL
- Torque: #12-#10: 35 lb-in, #8-#3: 100 lb-in, #2-3/0: 150 lb-in
- Dvakrat preverite vse povezave glede tesnosti in ustrezne izolacije.

Figure 2: Close-up of the circuit breaker's main label, detailing Cat No., Amp rating, Voltage, Pole configuration, Rating Plug Type, Lug Data, Wire Range, and Torque specifications.

Figure 3: Close-up of the circuit breaker's interrupting rating label, showing RMS Symmetrical Amps at various voltages (240V, 480V, 600V) and international standards.

Slika 4: Zadaj view of the GE SELA36AT0150 Circuit Breaker, showing the bolt-on mounting points and terminal connections.
4. Navodila za uporabo
The GE SELA36AT0150 circuit breaker is designed for simple operation, primarily acting as an ON/OFF switch and an automatic protective device.
4.1 Vklop/izklop
- Za vklop vezja ON, firmly push the handle to the "ON" position.
- Za vklop vezja IZKLOP, firmly push the handle to the "OFF" position.
4.2 Izklop in ponastavitev
If an overcurrent or short circuit condition occurs, the breaker will automatically "trip" to the center position (between ON and OFF) to protect the circuit. To reset a tripped breaker:
- First, move the handle completely to the "OFF" position. This resets the internal mechanism.
- Investigate and resolve the cause of the trip (e.g., overloaded circuit, short circuit).
- Once the issue is resolved, firmly push the handle to the "ON" position to restore power.
- If the breaker immediately trips again, do not attempt to reset it repeatedly. Consult a qualified electrician.
5. Vzdrževanje
Odklopniki običajno zahtevajo minimalno vzdrževanje. Vendar pa je za zagotovitev nadaljnjega varnega delovanja priporočljiv redni pregled.
- Vizualni pregled: Annually inspect the breaker for signs of physical damage, discoloration, or loose connections.
- Čiščenje: Keep the area around the breaker clean and free of dust and debris. Use a dry, non-conductive cloth for cleaning. Do not use liquids.
- Preverjanje povezave: Periodically (e.g., every 3-5 years, or as per local codes) have a qualified electrician check the tightness of terminal connections.
- Testiranje: For critical applications, periodic testing of the breaker's trip mechanism by a qualified professional may be required.
Opomba: Do not attempt to open or repair the circuit breaker. There are no user-serviceable parts inside.
6. Odpravljanje težav
Ta razdelek obravnava pogoste težave, na katere lahko naletite z odklopnikom.
| Težava | Možen vzrok | rešitev |
|---|---|---|
| Odklopnik se pogosto sproži. | Preobremenjen tokokrog, kratek stik, ozemljitvena napaka ali okvarjena naprava. | Zmanjšajte obremenitev tokokroga. Izključite naprave iz vtičnice. Preverite ožičenje glede poškodb. Če težava ne preneha, se posvetujte z usposobljenim električarjem. |
| Odklopnik se ne bo ponastavil. | Persistent fault (short circuit/overload) or internal breaker damage. | Ensure the handle is pushed fully to "OFF" before attempting to reset. If it still won't reset, do not force it. Call a qualified electrician. |
| Tokokrog ni priključen na napajanje, vendar je odklopnik vklopljen. | Loose connection, wiring issue, or internal breaker failure. | This indicates a serious issue. Immediately turn off the breaker and consult a qualified electrician. Do not attempt to diagnose or fix yourself. |
For any issues not covered here, or if troubleshooting steps do not resolve the problem, always contact a qualified and licensed electrician.
7. Specifikacije
Detailed technical specifications for the GE SELA36AT0150 Circuit Breaker:
| Atribut | Vrednost |
|---|---|
| Številka modela | SELA36AT0150 |
| Znamka | General Electric |
| Trenutna ocena | 150 Amps |
| voltage Ocena | 480 / 600 VAC |
| Število polov | 3 |
| Tip prekinilca | Standard, Current Limiting, Molded Case |
| Vrsta namestitve | Nosilec z vijaki |
| Interrupting Rating @ 240 VAC | 100,000 Amps |
| Interrupting Rating @ 480 VAC | 65,000 Amps |
| Interrupting Rating @ 600 VAC | 25,000 Amps |
| Rating Plug Type | SRPE150A |
| Rating Plug Inst. Adjustable Range | 450-1991 A (Lo to Hi) |
| Mere izdelka (D x Š x V) | 4" x 4" x 6.5" (približno) |
| Teža | 4.8 lbs (približno) |
| Prvič na voljo | 11. oktober 2012 |
8. Garancija in podpora
For specific warranty information regarding your GE SELA36AT0150 Circuit Breaker, please refer to the documentation provided at the time of purchase or contact General Electric directly. As a general guideline, electrical components typically come with a manufacturer's warranty covering defects in materials and workmanship.
For technical support, service, or to inquire about replacement parts, please contact General Electric customer service or visit their official webmesto. Obiščete lahko tudi Trgovina GE na Amazonu for more information on GE products.
Always ensure that any work on electrical systems is performed by qualified and licensed professionals.
9. Uradni videoposnetki izdelkov
No official product videos from the seller were found for this specific model in the provided data. For general product information or installation guides, please check the manufacturer's official webmestu ali pooblaščenim distributerjem.